MDM-B1(A)Series Distributed Complete Microprocessor-based Protections Measurement and Control Device

Introduction

MDM-B1(A)series Distributed Complete Microprocessor-based Protections Measurement and Control Device integrate functions of relay protection, measurement apparatus, telemetering, remote supervisory and remote control.

This product adopts unified module hardware design, unified module program structure and SMD technique etc, so it has the good electromagnetic compatibility, and can fully support DL/T667-1999 (IEC870-5-103) information interface standard.

MDM-B1(A)series products are applicable for power transmission line of 35KV and less, transformer, capacitor, HV motor, reactor, busbar, and generator etc.


Main Products

MDM-B1L(A)feeder protection, measurement and control device;
MDM-B1T(A)Distributed transformer protection, measurement and control device;
MDM-B1M(A)HV motor protection, measurement and control device;
MDM-B1C(A)Capacitor protection, measurement and control device;
MDM-B1D(A)Current differential relay;
MDM-B1P(A)Longitudinal directional relay based on optical fiber;
MDM-B1V(A)Multifunctional voltage relay;
MDM-ET1(A)Automatic throw-in unit from back-up power.

Functions

Function
Code
B1L
B1C
B1D
B1M
B1T
B1P
B1V
ET1
Protection funtion Ratio differential
87
Y
Longitudinal differential
87L
Y
Directional Over current
67P
Y
Over current with compound voltage
51S
Y
Y
Y
Y
Y
Y
Over current
51
Y
Y
Y
Y
Y
Y
Y
Negative sequence over current
46
Y
Zero sequence over current
50N
Y
Y
Y
Y
Y
Y
Y

  Zero sequence over voltage 59N     Y       Y  
Over voltage 59P   Y         Y  
Low voltage 27   Y   Y   Y Y  
Low frequency 81 Y         Y Y  
Excitation loss 40       Y        
Out of step 78       Y        
VT failure   Y   Y   Y Y Y  
TA failure       Y          
control Auto-recloser 79 Y       Y Y    
Automatic throw-in                 Y
Synchronous checking 25 Y         Y    
Breaker operation   Y Y Y Y Y Y   Y
Input channel(13)   Y Y Y Y Y Y Y Y
Output channel(9)   Y Y Y Y Y Y Y Y
measurement Current voltage frequency   Y Y   Y Y Y   Y
Power, power factor P,Q   Y Y   Y Y Y   Y
Power consumption   Y Y   Y Y Y   Y
communication
and user
interface
DL/T667 communication
(IEC60870-5-
103)
  Y Y Y Y Y Y Y Y
Event recorder (195times)   Y Y Y Y Y Y Y Y
Optical fibre communication interface   Y Y Y Y Y Y Y Y

Standard Satisfied

GB14285-93    "Technical code for relay protection and security automatic equipment"
DL/T587-96    "Management code for the operation of microprocessor-based
               relay protection "
DL478-92     "General specification for Static relay protection and security
              automatic device"
DL/T671-1999  "General specification for protective device of
               generator-transformer set based on microcomputer"
GB7261-2000             "Basic test method for relay and relay protective device"
GB4856                 " Electrical relay's insulation test"
GB6162                  "Static relay and protective device's electrical disturbance test"
GB/T14598.10-1996       "Fast instant disturbance test"
GB/T14598.13-1998       "1MHz pulses group disturbance test"
DL/667-1999             "Relay information interface standard"

Technical Parameters

    Power DC voltage: 88V~127V,176V~253V
    TA secondary rated current: 1A or 5A
    TV secondary normal voltage: 100/3 V,100V,300V
    AC rated frequency: 50Hz,60Hz
    Output relay contacts: ON 220V,5A continuously
                Off -L/R40ms,30WDC

Engineering Application

It has been widely used in projects of substation, power plants, power supply company, water conservancy, city planning, environmental protection and pump station of oil transmission etc.