FJY Feries Remote Terminal Unit Introduction
FJY series remote terminal unit is based on distributed multi-CPU concept and AC sampling technology. FJY series remote terminal unit mainly includes FJY-2 distributed AC sampling RTU, FJY-3 distributed RTU and FJY-3N RTU based on the Ethernet.
FJY series RTU is suitable for 35kV-220kV substations, switch yard, power plant, and hydraulic power station as measurement and supervisory control system.
This device passed the ministry appraisal in 1992 and received the second-class of Power Ministry Technology Progress Award.
Functional Characteristics
- The system employs distributed modular structural design, flexible configuration and is easy to expand.
- AC sampling and DC sampling compatible design, AC sampling two-meter method and three-meter method selectable, the measurement algorithm includes 15th harmonics, and the hardware circuit can be automatically adjusted.
- Power supply adopts AC and DC non-interference switching, redundancy and balanced current technology.
- Communication network adopts main/backup redundancy, main/backup modules automatically switchover to satisfy unmanned high reliability requirements.
- Teleindication circuit supports two-level isolation. Advanced signal extraction algorithm assures real-time performance and accuracy of change of state and event.
- Enriched history database can record RTU running condition, switch event, and telecontrol operation. The records will not be lost while losing power. Perfect self-diagnostic function is convenient for local or remote maintenance.
- Telecontrol multiple interlocking with special output checking function to assure its validity.
- Support various communication interfaces and protocols such as RS232, RS422, RS485, CANBUS, fiber-optic,
4F,SC1801, DNP3.0, IEC870-5-101, DL476, IEC870-5-104, and MODBUS, etc.
- Protocols of microprocessor-based relay protection, intelligent power-meter and other intelligent equipment can be selected from the panel.
- Anti lightning strike and anti transient interference design is suitable for severe working environment.
- Support GPS time hardware-synchronization to ensure clock synchronization across the network.
- LCD large screen(240
128 lattice), menu mode, easy for operation monitoring and maintenance.
Technical Parameters
-
DC input Capacity up to 512 points Input 5V, 0~10mA, 4~20mA
-
AC input Capacity 12 line/unit, can be extended to 96 lines AC value input 0~120V, 0~6A or 0~1A
-
Digital input Capacity up to 512 points Input First level: optoelectronic isolation 24V/5mA; second level: optoelectronic isolation 110V,220VDC
-
Digital output Capacity up to 384 Output mode idle contact output, DC220V/110V,5A
-
Analog output Capacity up to 32 Output mode 5V; 0~10mA; 4~20mA
-
Pulse input Capacity up to 512 points Input mode optoelectronic isolation, active/passive contact Output mode 32-bit binary coding
-
CPU: 80C196, 80296, 80486
-
Sampling precision: 0.5%
-
Measuring precision Voltage, current 0.2% P, Q 0.5% Frequency 0.01Hz
-
SOE resolution: 1ms
-
Time synchronization: by superior dispatch center or with GPS (employ second pulse synchronization and serial port combined mode).
-
Communication Rate 50~9600 Baud selectable Protocol Ministry issued CDT and IEC870-5-101,etc. Interface up to 5 RS232 synchronous/asynchronous ports, 3 RS232/RS422/RS485 asynchronous ports, 1 RS232 asynchronous port, 2 10M Ethernet
-
Working environment Temperature -15 ~55 Humidity <85% Barometric pressure 86~108kPa
-
Power source AC220V 20%, DC220V 20% or 110V 15%; AC and DC automatic switching; shunt balanced current
Engineering Application
Since this device was released in 1992, it has been applied in about 1500 substations and about 400 of them has become unmanned substations.
|