NS2000 Integrated Substation Automation System Introduction
NS2000 substation automation system is a new generation of multi-functional product developed and manufactured by NARI Technology Development Limited Company. The system consists of NS2000 computer supervisory and control system, NSC200 series communication control unit, NSD100 series line measuring and controlling unit, NSD200 series universal measuring and controlling unit, NSD500 series super high-voltage measuring and controlling unit, NSR200 and NSR300 series computer line protection unit, NSR500 series substation with whole computer protection unit, NSR600 series protection measuring and controlling unit, etc.
NS2000 system has advanced design, rational structure, flexible configuration, and reliable performance. It provides a total solution for customers from 500kV super high-voltage substation to 10kV switchyard.
Application Scope
1. Power system
- Substation of various voltage-level, switchyard and power plant.
- Substation with people on duty, few people on duty or no people on duty.
- Automation system of newly constructed substation and renovated old substation.
- Integrated installation mode, distributed assembly mode and compatible mode with characteristics of both.
- Protection and supervision independent configuration, protection and supervision integrated configuration.
- Intelligent equipment connection via field-bus, intelligent equipment connection via 10M/100M Ethernet.
2. Other fields
- Process supervision and control of subway, light rail, electrization railway and highway.
- Application in mine, petrochemical, metallurgy, haven, water supply, environment protection, and other industries.
Functions
1.Supervision function
- Data collection (status value, AC/DC analog value, pulse value) and processing
- Alarm and event recording
- History data recording
- Graphic function
- Display and print
- Report function
- Post disturbance review
2. Control function
- Support selective control function for multiple remote control centers
- Local control function for control room computer supervisory system
- Local control function for bay level equipment
- Synchronization testing and synchronized switch-on function
- Automatic control based on IEC1131 configuration
- Station-wide logic interlocking based on IEC1131 configuration
- Reactive power voltage automatic regulation
3. Protection function
- Line and feeder protection
- Transformer and reactor protection
- Electromotor protection
- Generator protection
- Capacitor protection
4. Configuration function
- System configuration
- Graphic configuration
- Database configuration
- PLC control function configuration based on IEC1131-3 standard
5. Communication function
- Multiple communication interfaces (RS232, RS422, RS485, CAN, LONWORKS, Ethernet, electric power carrier, cable, wireless and fiber etc) that support various of media and networks
- High speed data network communication with measuring and controlling unit
- Data network communication with various microprocessor-based relay protection
- Data network communication with various intelligent devices (computer-based DC system, intelligent power meter, intelligent fire alarm, and GPS, etc.)
6. Advanced functions
- Reactive power voltage automatic control
- Embedded PC-based maloperation prevention function
- Small current neutral grounding fault-line selection
- Operation ticket and maloperation prevention interlocking
- System diagnosis and self-recovery
- Remote supervision and maintenance
- Technical characteristics
- Opened system based on international standard
- Provide integrated automation total solution for substations of various voltage-level
- Employ 10M/100M self-adaptive redundant Ethernet and direct network link of bay-level equipment to improve system real-time ability and data transmission reliability
- Bay-level equipment realizes logic interlocking of station-wide control and operation not rely on station-control layer through network data sharing
- Based on real-time multi-task operating system software platform to improve system reliability and real-time performance
- Develop computer supervisory control system that combines business and real-time databases, is object oriented and with integrated graphic, model and database. The software's structure is both advanced and open. The system functions are practical and refined with friendly man-machine interface. It supports supervisory control of multiple substations and can be used in centralized control stations.
- Developed ladder diagram and execution software based on IEC1131-3 standard to realize standard PLC function
- Possess favorable EMC capability (its measuring and controlling unit for super high-voltage equipment has passed level-4 test).
Technical Parameters
1. System capacity
- Analog input 2048
- Digital input 4096
- KWH 512
- Digital output 1024
- Analog output 64(all expandable)
2. Data collection and control
- Measurement precision of analog value U,I: 0.2%, P, Q: 0.5%
- Cycle measurement
0.01HZ
- Percentage of digital input response accuracy 100%
- Sequence of event resolution 1ms
- Percentage of digital output and analog output accuracy 100%
3. Protection performance
- Group action time of the 1 segment distance relay <20ms
- High frequency or optic-fiber relay action time <30ms
- Impedance settings 0.01-30
(In=5A), 0.05-150 (In=1A)
- Fault location error <3%
- Minimum precise operating voltage 0.5V
- Minimum precise operating current 0.1In
- Maximum precise operating current 25In
- Settings error <5%
4. System response time
- Variation transfer of analog input
2s
- Change of state response time of digital input
2s
- Updating cycle of all digital input and remote pulse
30s
- Digital output and analog output command
2s
- Display response time
2s
- Display refresh time
3s
5. Fail-over time between host and backup computer 10s
6. Reliability index:
- MTBF
30000 hours
7. EMC performance (Note: NSD500 unit reaches level-4 completely)
- Static discharges anti-interference capability:
IEC61000-4-2 standard level 3.
- Radiated electromagnetic field anti-disturbance capability:
IEC61000-4-3 standard level 3
- Fast transient pulse group anti-interference capability:
IEC61000-4-4 standard level 3
- Impulse (Surge):
IEC61000-4-5 standard level 3
- Anti conductive disturbance of Electra-magnetic induction capability:
EC61000-4-6 standard level 3
- Power frequency magnetic field anti-interference capability:
IEC61000-4-8 standard level 3
Engineering Application
This system has been widely used in substations of various voltage-level and scales.



|